Solution de refroidissement liquide-liquide au niveau du rack

Capacité d'échange thermique : 50 kW, 80 kW
Aperçus
A compact, cabinet-based liquid-liquid cooling system, designed for small-scale or distributed liquid cooling scenarios (2+ liquid cooling cabinets). It uses dual liquid circuits (primary: cooling water; secondary: 25% ethylene glycol) for heat exchange, with 50kW-80kW cooling capacity and supports 19/21-inch standard racks.
Key CDU components (sensors, pumps) adopt redundant designs; it features small size, no major room modification, and easy expansion by single cabinet. Ideal for small-medium data centers, space-constrained edge computing facilities, and cold-plate liquid cooling scenarios needing flexible capacity increase.
  • Caractéristiques

  • Caractéristiques

  • Applications

  • Télécharger

Scénarios d'application

  • Small and medium-sized data centers, suitable for small-scale or distributed deployment of liquid-cooled computing scenarios (applicable to 2+ liquid cooling racks or above).
  • Edge computing facilities in space-constrained environments that require high-performance liquid cooling for edge computing.
  • Cold plate liquid-cooled computing application scenarios requiring flexible expansion, allowing capacity increase with a single rack as the minimum unit.

Product Features

  • Multi-Scenario Compatibility: Available in two size specifications (19-inch and 21-inch) to adapt to different application scenarios.
  • High Heat Density Deployment: The standard rack supports a power density ranging from 50kW to 200kW.
  • High Redundancy Design: Key components of the CDU (e.g., sensors, pumps) adopt redundant designs to maximize operational safety.
En savoir plus
Modèle SY-CDU-RK-50 SY-CDU-RK-80
Heat Exchange Capacity kW 50 80
Primary Side Circulation Medium / Cooling water Cooling water
Designed Inlet/Outlet Liquid Temperature 35/45 35/45
Circulation Flow Rate m³/h 4.32 6.91
Interface Size mm φ31.8*1.5 φ38.1*1.5
Water Pressure Drop KPa ≤100 ≤100
Secondary Side Circulation Medium / 25% ethylene glycol 25% ethylene glycol
Designed Inlet/Outlet Liquid Temperature 50/40 50/40
Outlet Liquid Temperature Range 35~50 35~50
Available Head KPa ≥120 ≥150
Circulation Flow Rate m³/h 4.56 7.29
Interface Size mm φ31.8*1.5 φ38.1*1.5
Puissance nominale kW 0.8 1.4
Net Weight kg 75 85
Overall Dimensions  mm 450*850*175 536*900*175
En savoir plus
En savoir plus
En savoir plus

Contactez-nous

Contactez-nous pour obtenir une assistance produit et technique

Veuillez activer JavaScript dans votre navigateur pour remplir ce formulaire.
WhatsApp

Laissez un message!

Laissez un message!

Veuillez activer JavaScript dans votre navigateur pour remplir ce formulaire.

Ouvrir une conversation sur WhatsApp ?

Annuler D'ACCORD